COMMAND DETAILS
47
:CONFigure:PROTection:POWer:LEVel
Channel Specific
Command
Description
Sets the power protection level for the
current/specific channel. The level can be set to
any applicable level or to the channel
maximum/minimum.
Syntax
:CONFigure:PROTection:POWer:LEVel
<NRf>[W]|MIN|MAX
Parameter
<NRf>
Power Protection Level
200
200Watts
200W
200Watts
MIN
Sets to the minimum level
MAX
Sets the power limit to the
maximum level
Example
:CONF:PROT:POW:LEV MAX
Sets the power limit to
102W (PEL2020)
Query Syntax
: CONFigure:PROTection:POWEr:LEVel? [MIN|MAX]
Return Parameter
<NRf>
Power protection level
1 unit = 1 watt
Returns the power
protection level in Watts.
MAX/MIN
Returns the allowable
maximum and minimum.
Query Example
:CONF:PROT:POW:LEV?
75
Power protection level is
at 75 watts.
:CONFigure:PROTection:UVP:CLEar
All Channel
Command
Description
Clears the under voltage power protection status.
Syntax
:CONFigure:PROTection:UVP:CLEar
Example
:CONF:PROT:UVP:CLE
Clears the under voltage
protection.