Example
:NSEQuence:LLOad ON
Turns Last Load on.
Query example
:NSEQuence:LLOad?
>Last Load: ON
Returns the last load state.
:NSEQuence:LAST
Set
Query
Description
Sets or queries the value of Last Load when Last
Load = ON. The unit depends on the Mode.
Syntax
:NSEQuence:LAST{<NR2>}
Query Syntax
:NSEQuence:LAST?
Parameter
<NR2>
current value(CC), resistance
value(CR), voltage value(CV), power
value(CP).
Return Parameter
<string>
Returns the value for the Last Load
in the following format:
Last:<NR2>
Example
:NSEQuence:LAST 1.000
Sets the value of Last Load to 1.000.
Query example
:NSEQuence:LAST?
>Last: 1.000
Returns the value of Last Load.
:NSEQuence:CHAin
Set
Query
Description
Sets or queries the next sequence in the chain.
Syntax
:NSEQuence:CHAin {<NR1>|OFF}
Query Syntax
:NSEQuence:CHAin?
Parameter
<NR1>
The sequence number of the next
sequence in the chain.
OFF
End the chain at the current
sequence.